PRECISION LaserCOMPACT
![]() |
Product literature How to buy |
The PRECISION LaserCOMPACT detector is specifically designed to be compatible with the PROACTIV Fire Alarm Control Panel (FACP) system. It also provides all the very early warning benefits of aspirated smoke detection. Advanced features include clean-air barrier to protect all detection chamber optics and an enhanced aspirator design incorporated into a smaller enclosure with a simplified display.
Description
The PRECISION LaserCOMPACT detector is made up of two parts; the front
cover and the main enclosure.
- The front cover supports 5 LEDs: Fire, Flow, Fault, OK and Filter.
- The main enclosure houses all the key components of the detectors.
The main enclosure includes:
- Laser detection chamber
- Main processor board
- Single-port entry with air flow sensor
- Termination Card, which includes power connections and PC connector for diagnostic purposes
- LaserCOMPACT aspirator
- Filter cartridge
- Air exhaust port.
All non-serviceable items, such as the main processor board and laser detector chamber, are mounted away from the general access area, protecting them during installation and routine service.
Features
- PRECISION™ compatible protocol for signaling and configuration
- Full product configurability via PROACTIV Fire Alarm Control Panel User Interface
- Protect areas up to 8000 sq.ft (approx 800 sq.m)
- Absolute smoke detection
- Wide sensitivity range
- Single pipe inlet
- Dual stage dust filter
- Airflow monitoring
- AutoLearn™
- Simple mounting design
- Event log capable of storing up to 10,240 events.
- Smoke level alarms and faults with date time stamp.
|